Directive: Major and minor alterations
Persona
Technologies
This Directive is being issued by a provincial safety manager pursuant to section 30 of the Safety Standards Act.
General details
This Directive is issued to all Licensed Elevating Devices Contractors to clarify requirements 25 of the EDSR regarding Submission and Filing of Technical Information Documents for minor or major alteration of an existing elevating device.
Please download a copy for your records or update your bookmarks.
Specific details
This Directive is effective on September 30, 2011.
As per requirement 25 (1) of the EDSR before the installation of a major or minor alteration of an existing elevating device may begin, a technical information package for the elevating device must be submitted to, and filed with, the provincial safety manager in the required form. Installation may not begin until a Design Registration Installation Permit has been issued.
Definitions:
Alteration: any change to equipment, including its parts, components, and/or subsystems, other than maintenance, repair, or replacement.
Replacement: the substitution of a device or component and/or subsystems, in its entirety, with a unit that is basically the same as the original for the purpose of ensuring performance in accordance with applicable Code requirements (see CSA B44-07 8.6.12.5 where replacement of specific components constitutes an alteration).
For Major Alterations:
- The technical information package submitted under subsection (1) must include the seal of a BC professional engineer approving the design drawings and specifications for a major alteration to an existing elevating device, and the professional engineer must verify the accuracy of the contents of the technical information package.
- Also as per requirement 12 (1) (b) of the EDSR a licensed elevating device contractor must ensure that an elevating device undergoes an acceptance inspection by a safety officer when the elevating device has undergone a major alteration prior to the device returning to service. In order to assist contractors in defining major alterations a list has been attached to this directive (Table A).
For Minor Alterations:
A) As per the EDSR definitions "minor alteration" means an alteration to an elevating device that is not a "major alteration". Therefore all alterations that do not fall under the list of major alterations will be considered a minor alteration. Table B lists the minor alterations that will require inspection.
Table A
ELECTRIC ELEVATORS |
|||
# |
MAJOR ALTERATIONS DETAILS |
Type of Inspection Required |
Code Reference |
1 |
Hoistway enclosure walls (Structural) |
Special Inspection (S.I.) |
8.7.2.1.1 |
2 |
Location of the C.W. |
Acceptance (A.) |
8.7.2.3 |
3 |
Vertical clearances |
A |
8.7.2.4 |
4 |
Horizontal clearances |
A |
8.7.2.5 |
5 |
Protection of space below hoistway |
A |
8.7.2.6 |
6 |
Machine beams & foundation |
A |
8.7.2.9 |
7 |
Hoistway entrances & openings |
A |
8.7.2.10 |
8 |
Hoistway door locking devices & access switches |
A |
8.7.2.11 |
9 |
Car enclosure, car doors & gates |
S.I. |
8.7.2.14 |
10 |
Car frame & platform |
A |
8.7.2.15 |
11 |
Capacity, loading, classification |
A |
8.7.2.16 |
12 |
Change in rise & rated speed |
A |
8.7.2.17 |
13 |
Car & CW safeties |
A |
8.7.2.18 |
14 |
Speed governors & governor ropes |
A |
8.7.2.19 |
15 |
Ascending car & unintended movement |
A |
8.7.2.20 |
16 |
Suspension ropes & their connections |
A |
8.7.2.21 |
17 |
Counterweights |
S.I. |
8.7.2.22 |
18 |
Buffers & bumpers |
A |
8.7.2.23 |
19 |
Guide rails, supports & fastenings |
A |
8.7.2.24 |
20 |
Driving machines & sheaves |
A |
8.7.2.25 |
21 |
Operating devices & control equipment |
A |
8.7.2.27 |
22 |
FEO devices |
A |
8.7.2.28 |
HYDRAULIC ELEVATOR |
|||
# |
MAJOR ALTERATIONS DETAILS |
Type of Inspection Required |
Code Reference |
23 |
Hoistway enclosure walls (Structural) |
S.I. |
8.7.3.1.1 |
24 |
Location of the C.W. |
A |
8.7.3.3 |
25 |
Vertical clearances |
A |
8.7.3.4 |
26 |
Horizontal clearances |
A |
8.7.3.5 |
27 |
Protection of space below hoistway |
A |
8.7.3.6 |
28 |
Machine beams & foundation |
A |
8.7.3.9 |
39 |
Hoistway entrances & openings |
A |
8.7.3.10 |
30 |
Hoistway door locking devices & access switches |
A |
8.7.3.11 |
31 |
Car enclosure, car doors & gates |
S.I. |
8.7.3.14 |
32 |
Safeties (car/CW gripper) |
A |
8.7.3.15 |
33 |
Speed governors & governor ropes |
A |
8.7.3.16 |
34 |
Change in type of service |
A |
8.7.3.17 |
35 |
Change in class of loading |
A |
8.7.3.18 |
36 |
Carrying of passenger |
A |
8.7.3.19 |
37 |
Increase in rated load |
A |
8.7.3.20 |
38 |
Increase in deadweight of the car |
A |
8.7.3.21 |
39 |
Change in rise or rated speed |
A |
8.7.3.22 |
40 |
Hydraulic cylinder |
A |
8.7.3.23 |
41 |
Hydraulic plungers |
A |
8.7.3.23.2 |
42 |
Plunger Gripper |
A |
8.7.3.23.7 |
43 |
Suspension ropes & their connections |
A |
8.7.3.25 |
44 |
Counterweight alteration |
A |
8.7.3.26 |
45 |
Buffers & bumpers |
A |
8.7.3.27 |
46 |
Guide rails, supports & fastenings |
A |
8.7.3.28 |
47 |
Tanks |
A |
8.7.3.29 |
48 |
Operating devices & control equipment |
A |
8.7.3.31 |
ESCALATORS AND MOVING WALKS |
|||
# |
MAJOR ALTERATIONS DETAILS |
Type of Inspection Required |
Code Reference |
51 |
Relocation of Escalators |
A |
8.7.6.1.2 |
52 |
Relocation of Moving walks |
A |
8.7.6.2.2 |
53 |
Construction Requirements for Escalators |
A |
8.7.6.1.5 |
54 |
Construction Requirements for Moving Walks |
A |
8.7.6.2.5 |
55 |
Handrails of an Escalator |
A |
8.7.6.1.6 |
56 |
Handrails of a Moving Walk |
A |
8.7.6.2.6 |
57 |
Escalators Step System |
A |
8.7.6.1.7 |
58 |
Moving Walk Treadway System |
A |
8.7.6.2.7 |
59 |
Escalators Combplate |
A |
8.7.6.1.8 |
60 |
Moving Walk Combplate |
A |
8.7.6.2.8 |
61 |
Escalators Trusses and Girders |
A |
8.7.6.1.9 |
62 |
Moving Walk Trusses and Girders |
A |
8.7.6.2.9 |
63 |
Escalators Step Wheel Tracks |
A |
8.7.6.1.10 |
64 |
Moving Walk Tracks |
A |
8.7.6.2.10 |
65 |
Escalators Rated Load and Speed |
A |
8.7.6.1.11 |
66 |
Moving Walk Rated Load and Speed |
A |
8.7.6.2.11 |
67 |
Escalators Driving Machine, Motor, and Brake |
A |
8.7.6.1.12 |
68 |
Moving Walk Driving Machine, Motor, and Brake |
A |
8.7.6.2.12 |
69 |
Escalators Operating and Safety Devices |
A |
8.7.6.1.13 |
70 |
Moving Walk Operating and Safety Devices |
A |
8.7.6.2.13 |
71 |
Escalators Lighting, Access, and Electrical Work |
A |
8.7.6.1.14 |
72 |
Moving Walks Lighting, Access, and Electrical Work |
A |
8.7.6.2.14 |
73 |
Escalators Controller |
A |
8.7.6.1.16 |
74 |
Moving Walks Controller |
A |
8.7.6.2.15 |
ELECTRIC AND HYDRAULIC ELEVATOR / ESCALATORS AND MOVING WALKS |
|||
# |
MINOR ALTERATIONS DETAILS |
Type of Inspection Required |
Code Reference |
1 |
Machine room & machine space alteration |
S.I. |
8.7.2.7 |
2 |
Electrical equipment, wiring, pipes in Hwy & M/R |
S.I. |
8.7.2.8 |
3 |
Alteration of Valves |
Hydraulic Elevator Tests Declaration |
8.7.3.24 |
4 |
Restricted Access on Car Calls |
Restricted Access and FEO Phase II Operation Tests Declaration |
|
5 |
Protection of floor opening of an Escalator |
S.I. |
8.7.6.1.3 |
6 |
Protection of floor opening of a Moving Walks |
S.I. |
8.7.6.2.3 |
7 |
Protection of Trusses and Machinery Spaces Against Fire on Escalators |
S.I. |
8.7.6.1.4 |
8 |
Protection of Trusses and Machinery Spaces Against Fire on Moving Walks |
S.I. |
8.7.6.2.4 |
9 |
Entrance and Egress on Escalators |
S.I. |
8.7.6.1.15 |
10 |
Driving Machine and Sheaves (Guarding of Equipment) |
S.I. |
8.7.2.25.1(a) |
11 |
Internal Cab Modernization |
S.I. |
See Information Bulletin no: B-L4 110803 4 |
Houssam Hamze
A/Provincial Safety Manager, Elevating Devices