This Directive is provided to clarify the requirements for installation of propane regulators in vapour service in order to ensure the regulators are not subjected to propane liquid.

Specific details

Clause 4.5.2 in both the CSA B149.1- Natural Gas and Propane Installation Code and B149.2- Propane Storage and Handling Code state: 

The use of an appliance, an accessory, a component, equipment, or material shall be prohibited where a hazard is created.

Clause 5.1.2 of the CSA B149.1 requires that propane gas systems shall be installed to prevent liquefaction of propane.

Liquefaction of propane can create a hazard. First-stage and integral two-stage propane vapour regulators that are not installed directly on a propane container can be subjected to liquid propane due to no-flow conditions and/or changes in ambient temperatures if they are installed below the liquid level of the supply container. Vapour service regulators are not designed to regulate propane liquid, and may be damaged by it, or may pass liquid leading to hazardous conditions downstream.

These regulators must be installed above the maximum liquid level of the supply container(s), and have the supply connection oriented to allow for any liquid to drain back to the container.

Second-stage regulators installed in areas of the province where the ambient temperature may permit reliquification at the supplied intermediate pressure are to be installed in such a manner preventing the accumulation of liquid at the regulator’s inlet.

 

 

Brad Wyatt
Provincial Safety Manager, Gas 

 

 

References:
Safety Standards Act
Gas Safety Regulation
Safety Standards General Regulation
CSA B149.1 - Natural gas and propane installation code 
CSA B149.2 - Propane storage and handling code

Attachment Size
d-ga_2012-03-2016-rev1.pdf 33.17 KB