Propane regulator installation

Directive

Directive: Propane regulator installation

October 1, 2022

Directive
Gas

Reference Number:

D-GA 2012-03

Revision Number:

Revision 2



Scope

This directive is provided to clarify the requirements for installation of propane regulators in vapour service in order to ensure the regulators are not subjected to propane liquid.

Details 

Clause 4.5 in both CSA B149.1 Natural gas and propane installation code and B149.2 Propane storage and handling code, state: “The use of an appliance, an accessory, a component, equipment, or material shall be prohibited where a hazard is created”.

Clause 5.1 of CSA B149.1 requires that propane gas systems shall be installed to prevent liquefaction of propane.

Liquefaction of propane can create a hazard. First-stage and integral two-stage propane vapour regulators that are not installed directly on a propane container can be subjected to liquid propane due to no-flow conditions and/or changes in ambient temperatures if they are installed below the liquid level of the supply container. Vapour service regulators are not designed to regulate propane liquid, and may be damaged by it, or may pass liquid leading to hazardous conditions downstream. 

These regulators must be installed above the maximum liquid level of the supply container(s) and have the supply connection oriented to allow for any liquid to drain back to the container. Second-stage regulators installed in areas of the province where the ambient temperature may permit reliquification at the supplied intermediate pressure are to be installed in such a manner preventing the accumulation of liquid at the regulator’s inlet.

  

Vicky Kang
Manager, Energy
Provincial Safety Manager, Gas

 

References: 
Safety Standards Act
Gas Safety Regulation
Safety Standards General Regulation
CSA B149.1 - Natural gas and propane installation code
CSA B149.2 - Propane storage and handling code

Back To Top

As a province-wide organization, Technical Safety BC respectfully recognizes that its employees live and work on the traditional and unceded territories of the many Indigenous Nations that have thrived throughout British Columbia since time immemorial.

Technical Safety BC collects information for the purposes of administering the Safety Standards Act. That Act, along with the Freedom of Information and Protection of Privacy Act, constitutes the authority to collect such information. If you have questions about the collection, use, or disclosure of this information, contact the Senior Records, Information and Privacy Analyst for Technical Safety BC at 1 866 566 7233.