Ammonia refrigeration plant compressor develops cracks, releases oil and ammonia into the mechanical room

Incident Investigation

Ammonia refrigeration plant compressor develops cracks, releases oil and ammonia into the mechanical room

August 14, 2017

Boiler, PV and Refrigeration

Reference Number:

5620262



Incident overview

½” Service Valve installation threads broke on Ammonia Refrigeration Compressor, causing oil and some ammonia to leak from the broken threaded area of the Service Valve into the machinery room.

Regulated industry sector

Boilers, PV & Refrigeration – Refrigeration system.

Location

Chilliwack

Investigation Conclusions

Site, system and components

The refrigeration system circulates ammonia from compressors, which makes the gas hot and raises its pressure, enabling it to hold larger amounts of heat. The condenser which is installed outside of the building changes the gas to a liquid, allowing it to lose its heat in the process, while the expansion device turns the liquid back into a cold gas, releasing most of the heat it held while circulating thru other components on the system. The ½” service valve in question is installed on a portion of the compressor piping that operates in vacuum while the compressor is running, the valve is intended for bypassing a check valve during compressor servicing.

Failure scenario(s)

The threads of a ½” service valve on the piping of the compressor of a new ammonia refrigeration plant, cracked apart and released oil and some ammonia into the mechanical room. System shutdown was initiated once a leak was detected.

Facts and evidence

Broken threads on a ½” Service Valve, see attached picture provided from the Licensed Contractor that was called in to repair the issue, the system was shut down by the attending Chief Engineer of the plant.
The Licensed Contractor stated there has never been an issue with these types of valves, and possibly the threads were damaged during shipping of the new compressor to the plant or during construction.

Causes and contributing factors

It is highly probable, that the broken threads of the ½” Service Valve on the compressor caused the leakage.

Impact

  • Injury
    • Qty injuries: None
    • Injury description: None
    • Injury rating: None
  • Damage
    • Damage description: Broken ½” Service Valve installation threads on Ammonia Refrigeration Compressor.
    • Damage rating: Minor

Incident rating

Minor