Corrosive Condensate Damages Boilers and Venting System

Incident Investigation

Corrosive Condensate Damages Boilers and Venting System

March 24, 2023

Gas

Reference Number:

II-1525788-2023(#33751)



Location: Quesnel, BC
Regulated industry sector: Gas – Natural gas system

 

Incident Overview

Two boilers and their natural draft venting systems were discovered to be corroded and damaged beyond repair. Investigation found that a bypass mixing valve was left in the off position, causing the inlet water temperature to be too low. This resulted in corrosive condensate forming in the boiler combustion chamber and causing corrosion damage to the venting system.