Cracked compressor discharge line leaks refrigerant

July 20, 2017

Boiler, PV and Refrigeration

Reference Number:

5619043



Incident overview

The P24 ice maker compressor discharge line cracked resulting in most of the refrigerant charge being lost, and a minor injury to one employee who entered the room. (Inhalation and subsequent discomfort)

Regulated industry sector

Industrial

Location

Duncan, BC

Investigation conclusions

Site, system and components

Compressor discharges high pressure, high temperature gas through this line to the evaporative condenser.

Failure scenario(s)

Years of vibration from the compressor is the likely cause of the copper line cracking.

Facts and evidence

There are no other indications other than what is noted above as contributing factors that lead to this incident.

Impact

  • Injury
    • Qty injuries: 1
    • Injury description: Employee felt weak, dizzy, and faint. Was transported to hospital and later released. Returned to work the next day, therefore no lost time.
    • Injury rating: Minor
    Damage
    • Damage description: Compressor discharge line cracked, resulting in R22 refrigerant loss of containment.
    • Damage rating: Minor

Incident rating

Minor