Small Ammonia Leak Occurs at Athletic Club

Incident Investigation

Small Ammonia Leak Occurs at Athletic Club

April 9, 2024

Boiler, PV and Refrigeration

Reference Number:

II-1695882-2024 (#45521)



Location: North Vancouver
Regulated industry sector: Boilers, PV & refrigeration - Refrigeration system

 

Incident overview

An ammonia leak occurred inside the machinery room of a public athletic club with indoor ice facilities. The leak happened during decommissioning work of an ammonia refrigeration condenser by a licensed refrigeration contractor and resulted in the facility enacting their Ammonia Release Emergency Protocol. The incident was likely caused because the contractor didn’t properly purge and vacuum the oil pot and drop leg to remove all the ammonia from the refrigeration system before cutting the pipe.