BC Electrical Code - Section 14 - Protection and Control

Directive

Directive: BC Electrical Code - Section 14 - Protection and Control

June 11, 2020

Directive
Electrical

Reference Number:

D-EL 2016-07

Revision Number:

Revision 1



This directive is being issued by a provincial safety manager pursuant to section 30 of the Safety Standards Act.

 

A: Protective Devices
14-106 Location and Grouping

Overcurrent devices shall be located in readily accessible places, except as provided for elsewhere in the BC Electrical Code (BCEC), and shall be grouped where practicable.

Interpretation:

Rules 14-106 and 14-406, of the BCEC require that overcurrent and control devices must be readily accessible. Readily accessible is defined in Section 0 of the BCEC as:

“capable of being reached quickly for operation, renewal, or inspection, without requiring those to whom ready access is a requisite to climb over or remove obstacles or to resort to portable ladders, chairs, etc.”

This definition does not require the location to be within a particular occupancy where utilization equipment, or branch circuit overcurrent devices are installed.

  1. Other than dwelling units, branch circuit overcurrent devices are interpreted as being readily accessible when located within the occupancy that the circuits supply.

In apartments and similar buildings, the feeder disconnecting means shall be located where the feeder receives its supply and may include additional disconnecting means at the panelboard.

  1. Access to the common area shall not be impeded by barriers. Access through a door is considered readily accessible when the key for the door is readily accessible.
  2. This requirement is intended to improve safety by providing ready access to the disconnecting means controlling electrical equipment inside the occupancy.

 

B: Control Devices
14-406 Location of Control Devices

Rule:

  1. Control devices, with the exception of isolating switches, shall be readily accessible.
  2. Remotely controlled devices shall be considered to be readily accessible if the means of controlling them are readily accessible.

Interpretation:

  1. Readily accessible is interpreted to be in the occupancy that the circuits serve and must be capable of being reached quickly for operation, renewal, or inspection, without requiring those to whom ready access is a requisite to climb over or remove obstacles or to resort to portable ladders, chairs, etc.
  2. Devices such as ground fault circuit interrupters (GFCI) and arc fault circuit interrupters (AFCI) as required by the BCEC are considered to have control properties and shall be readily accessible.
  3. When these devices are integral with an overcurrent device (breaker), they are considered readily accessible in which case the interpretation outlined in A above applies.
  4. When these devices are located in a receptacle configuration, including devices without a Diagram 1 or 2 configuration, such as faceless types, they too shall be readily accessible.

 

Vicky Kang
Manager, Energy
Provincial Safety Manager, Electrical

 

 

References:
Safety Standards Act
Electrical Safety Regulation
Safety Standards General Regulation

Back To Top

As a province-wide organization, Technical Safety BC respectfully recognizes that its employees live and work on the traditional and unceded territories of the many Indigenous Nations that have thrived throughout British Columbia since time immemorial.

Technical Safety BC collects information for the purposes of administering the Safety Standards Act. That Act, along with the Freedom of Information and Protection of Privacy Act, constitutes the authority to collect such information. If you have questions about the collection, use, or disclosure of this information, contact the Senior Records, Information and Privacy Analyst for Technical Safety BC at 1 866 566 7233.