BC Electrical Code Section 26 (Installation of Electrical Equipment)
Directive
BC Electrical Code Section 26 (Installation of Electrical Equipment)
February 29, 2016
Reference Number:
D-EL 2016-01
Revision Number:
02
Date of Issue: June 11, 2020
This directive provides clarification on the interpretation of Section 26 of the BC Electrical Code. It provides instructions about the location of panelboards, placement of receptacles in closets, balconies and counters, altering existing branch circuits, and the location of outlet branch-circuit-type arc-fault interrupters.
26-602 Panelboards in Dwelling Units
Subrule 1):
"A panelboard shall be installed in every dwelling unit except for
- dwelling units in hotels and motels; and
- dwelling units that have been created by subdivision of a single dwelling and are not individually metered for electrical power consumption.”
Interpretation:
A suite created by the subdivision of a dwelling unit, that is not individually metered, does not require a panelboard within the suite.
Subrule 1) b) is interpreted as meaning subdivision of a single dwelling only.
26-722 Receptacles for Dwelling Units
Subrule a):
“…except as otherwise provided for in this Code, in dwelling units, duplex receptacles shall be installed in the finished walls of every room or area, other than bathrooms, hallways, laundry rooms, water closet rooms, utility rooms, or closets, so that no point along the floor line of any usable wall space is more than 1.8 m horizontally from a receptacle in that or an adjoining space, such distance being measured along the floor line of the wall spaces involved;”
Interpretation:
This subrule does not require nor prohibit a receptacle in a closet.
26-722 Receptacles for Dwelling Units
Subrule b):
“…at least one duplex receptacle shall be provided in each area, such as a balcony or porch, that is not classified as a finished room or area in accordance with Item (a)”
Interpretation:
Receptacles installed to meet the requirements of this subrule are considered to be provided in each area, such as a balcony or porch, only if they are located within the area and readily accessible from floor level.
26-722 Receptacles for Dwelling Units
Subrule d)iii):
“…a sufficient number of receptacles (5-15R split or 5-20R) along the wall at counter work surfaces (excluding sinks, built-in equipment, and isolated work surfaces less than 300 mm long at the wall line) so that no point along the wall line is more than 900 mm from a receptacle measured horizontally along the wall line”
Interpretation:
- Construction methods or materials do not affect the requirement in this rule.
- This rule does not require receptacles to be installed within a wall space.
- Alternatives such as in-counter “pop-up” receptacles, surface mounted receptacles, or receptacles mounted to the underside of the cupboard are acceptable, provided they are approved for the purpose, accessible, and installed as close as feasible to the wall.
26-658 Arc-Fault Protection of Branch Circuits for Dwelling Units
Subrule (2):
“Notwithstanding subrule 1), the entire branch circuit need not be provided with arc-fault protection where
- an outlet branch-circuit-type arc-fault circuit interrupter is installed at the first outlet on the branch circuit, and
- the wiring method for the portion of the branch circuit between the branch circuit overcurrent device and the first outlet consists of metal raceway, armoured cable, or non-metallic conduit or tubing”
Interpretation:
When an outlet branch-circuit-type arc-fault interrupter is used, it shall be accessible for testing in accordance with manufacturer’s instructions.
Provincial Safety Manager
References:
Safety Standards Act
Electrical Safety Regulation
Safety Standards General Regulation